Calculate liquid line subcooling to verify your condenser refrigerant charge. Enter the condenser saturation temperature and liquid line temperature for an instant subcooling reading.
Subcooling is the temperature difference between the saturated liquid refrigerant at condenser pressure and the actual liquid line temperature leaving the condenser. It ensures a solid column of liquid at the expansion device, preventing flash gas.
Target subcooling is typically 5–12°C for TXV systems. Correct subcooling ensures the expansion device receives fully liquid refrigerant for proper metering and evaporator performance.
Target subcooling is typically 5–12°C for TXV systems. Always check the manufacturer's specification for the exact target, as it varies by unit and refrigerant.
Low subcooling indicates an undercharge or a restriction before the expansion device. The system doesn't have enough refrigerant to fully condense and subcool the liquid.
High subcooling indicates an overcharge or a restriction in the liquid line. Too much refrigerant backs up in the condenser, increasing subcooling.
Calculate evaporator superheat from suction line and saturation temperatures.
Convert refrigerant pressure to temperature and vice versa for common refrigerants.
Calculate total refrigerant charge including factory charge and pipe length allowance.
Calculate the extra refrigerant needed for additional pipe length beyond standard.