Calculate the current (amps) for a single-phase electrical load from the power (kW), voltage, and power factor. Essential for cable and circuit breaker sizing.
Single-phase current: Amps = kW × 1000 ÷ (V × PF). For example, 3 kW at 230V with PF 0.9 = 14.5 amps.
UK single-phase supply is 230V at 50Hz. Most domestic circuits are rated at 13A (socket ring) or 16A–32A (dedicated circuits).
3 kW at 230V single-phase with PF 0.9 = approximately 14.5 amps. This would require a 16A circuit breaker and appropriately sized cable.
UK single-phase supply is 230V at 50Hz (nominal). The actual voltage may vary between 216V and 253V in accordance with BS EN 50160.
Convert kilowatts to amps for single-phase and three-phase loads.
Calculate three-phase current from kW, voltage and power factor.
Calculate voltage drop in cables from current, length and conductor size.
Convert apparent power (kVA) to real power (kW) using power factor.