Calculate chiller cooling capacity from the chilled water flow rate and flow/return temperature difference. Get results in kW, tons of refrigeration, and BTU/hr.
Chiller capacity is calculated as: Q (kW) = Flow Rate (L/s) × 4.18 × ΔT (°C), where 4.18 is the specific heat capacity of water in kJ/kgK.
This is the fundamental formula for field-verifying chiller performance. By measuring the flow rate and temperatures, you can confirm the chiller is delivering its rated capacity.
Use an ultrasonic flow meter clamped to the pipe, or read the value from the BMS if a flow sensor is installed. Alternatively, use the pump curve and differential pressure.
1 ton of refrigeration (TR) = 3.516 kW = 12,000 BTU/hr. It originates from the cooling effect of melting 1 ton of ice in 24 hours.